RF-18-253 (2) A, .1
INGINURING
4225 SW 71 Ave Miami. A 33155
Tel: 786-398-9179 fax: 786-800-2627
a 1 roofinspectioni,gmail.com
LAB CERTIFICATION #16-0510.15
SITE SPECIFIC INFORMATION
UPLIFT TEST-TAS #106
03/16/2018
Roofing Contractor AIG ROOFING Permit# RF-2-18-253
Job Address 1200 NE 97 ST
Owner's Name MARIA CONTRERAS ELI BRAVO
Type of Tile FLAT 13" Date Installed
Approximate Roof Height 12' feet Roof Pitch 3/12 Type of Access to Roof LADDER
Approximate Square Footage of Roof 30 ft2 Required Testing Force 35 Lbs
Date Tested 03/14/2018 Number of Tests 71 Testing Equipment F.G.E.100
Contact Name GUILLERMO Phone# 786-301-9917
LOCATION #OF TEST PASS #OF TEST FAIL
Corner 9 Tests 9 Pass Test Fail
Perimeter 12 Tests 12 Pass Test Fail.
Field 30 Tests 30 Pass Test Fail
Ridge 20 Tests 20 Pass Test Fail
TOTAL 71 Tests 71 Pass 0 Test 0 Fail
IN ACCORDANCE WITH THE CRITERIA OF PROTOCOL PA 106,THIS ROOF ASSEMBLY HAS PASSED THE STATIC UPLIFT QUALITY CONTROL TEST.THIS TAS 106 TEST HAS BEEN PERFORMED IN FULL ACCORDANCE TO THE
REQUIREMENTS OF DADE COUNTRY,WITH NO DEVIATIONS.THIS REPORT IS NOT GUARANTEED IN CASE OF CASE OF NATURAL DISASTERS.THIS REPORT IT IS NOT VALID FOR INSURANCE CLAIMS.
YENAN T. LEYVA
PE 67416
r.
y
v t"*
Job Address 1200 NE 97 ST
Permit Number RF-2-18-253