RF-17-2856, ENGINEERING 4225 SW 71 Ave Miami. FI 33155 Tel: 786-398-9179 Fax: 786-800-2627 al roofinspection angmail.com LAB CERTIFICATION #16-0510.15 SITE SPECIFIC INFORMATION UPLIFT TEST - TAS #106 03/06/2018 Roofing Contractor CITY ROOFING Job Address 1384 NE 104 St Miami Shores, FI 33138 Owner's Name JOSE AIGLESIAS & W BEATRICE E Type of Tile EAGLE BELIER Approximate Roof Height 24' feet Approximate Square Footage of Roof Date Tested 03/05/2018 Contact Name CANDY Roof Pitch 4/12 25 ft2 Number of Tests 62 Permit Date Installed Type of Access to Roof LADDER Required Testing Force 35 Lbs Testing Equipment F.G.E.100 Phone # 305-248-2994 LOCATION # OF TEST PASS # OF TEST FAIL Corner 6 Tests 6 Pass Test Fail Perimeter 14 Tests 14 Pass Test Fail Field 25 Tests 25 Pass Test Fail Ridge 17 Tests 17 Pass Test Fail TOTAL 62 Tests 62 Pass o Test 0 Fail IN ACCORDANCE WITH THE CRITERIA OF PROTOCOL PA 106, THIS ROOF ASSEMBLY HAS PASSED THE STATIC UPLIFT QUALITY CONTROL TEST. THIS TAS 106 TEST HAS BEEN PERFORMED IN FULL ACCORDANCE TO THE REQUIREMENTS OF DADE COUNTRYNO DEVIATIONS. THIS REPORT 15 NOT GUARANTEED IN CASE OF CASE OF NATURAL DISASTERS. THIS REPORT Fr IS NOT VALID FOR INSURANCE CLAIMS. ip_ YENAN «T:• ;LEYVA •'i PE 67416", { Job Address k1384 NE 104 St Miami Shores, FI 33138 Permit Number RF -12-17-2856 Roof Drawing j. 1 . 45 14 52 47' 20 25 6 53 4 is 51 50 1 49 13 16 17 18 14 41 ' 11 ..�r: $ 61 i2 54 39 44 SS9 46 42 62 43 SS 7 . Inspection Worksheet Miami Shores Village 10050 N.E. 2nd Avenue Miami Shores, FL Phone: (305)795-2204 Fax: (305)756-8972 inspection Number: INSP-293309 Permit Number. RF -12-17-2856 Scheduled Inspection Date: March 07, 2018 Inspector: Alvarez, Manny Angel Owner: IGLESIAS, BEATRICE E GARCIA & �r�ec Job Address:13847NE 104 Street . Miami Shores, FL 33138 - Project: <NONE> Contractor: CITY ROOFING AND CONSTRUCTION INC Permit Type: Roof Inspection Type: Final Roof Work Classification: Tile Phone Number (786)853-4783 Parcel Number 1122320320260 Phone: (305)248-2994 Building Department Comments RE -ROOF TILE TO TILE Infractio Passed Comments INSPECTOR COMMENTS False Passed Failed Correction Needed Re -Inspection Fee No Additional Inspections can be scheduled until re -inspection fee is paid. Inspector Comments T March 06, 2018 For Inspections please call: (305)762-4949 Page 13 of 37 Project Address Miami Shores Village 10050 N.E. 2nd Avenue NE Miami Shores, FL 33138-0000 Phone: (305)795-2204 Permit Perm/t NO. RE -12-17-2856 Permit Type: Roof Work Classification: Tile Permit Status: APPROVED Issue Date: 12112/2017 Expiration: 06/10/2018 Parcel Number Applicant 1384 NE 104 Street Miami Shores, FL 33138- 1122320320260 Block: Lot: BEATRICE E GARCIA & JOSE I( Owner Information Address Phone Cell BEATRICE E GARCIA & JOSE 1384 NE 104 Street MIAMI SHORES FL 33138-2662 (786)853-4783 1384 NE 104 Street MIAMI SHORES FL 33138-2662 Contractor(s) Phone Cell Phone CITY ROOFING AND CONSTRUCTION (305)248-2994 (305)218-7901 Valuation: $ 25,000.00 Total Sq Feet: 2500 Type of Work: Re Roof Additional Info: RE -ROOF TILE TO TILE Classification: Residential Scanning: 3 Fees Due Bond Type - Contractors Bond CCF DBPR Fee DCA Fee Education Surcharge Permit Fee - New Roof Scanning Fee Technology Fee Total: Amount $500.00 $15.00 $4.50 $3.00 $5.00 $300.00 $9.00 $20.00 $856.50 Pay Date Invoice # 12/04/2017 12/12/2017 Bond #: 3592 Pay Type RF -12-17-65810 Credit Card Credit Card Amt Paid Amt Due $ 50.00 $ 806.50 $'806.50 $ 0.00 Available Inspections: Inspection Type: Up Lift Report Tin Cap Final Roof Tile In Progress Renailing Affidavit Review Roof Cap Sheet In consideration of the issuance to me of this permit, I agree to perform the work covered hereunder in compliance with all ordinances and regulations pertaining thereto and in strict conformity with the plans, drawings, statements or specifications submitted to the proper authorities of Miami Shores Village. In accepting this permit I assume responsibility for all work done by either myself, my agent, servants, or employes. I understand that separate permits are required for ELECTRICAL, PLUMBING, MECHANICAL, WINDOWS, DOORS, ROOFING and SWIMMING POOL work. OWNERS AFF construction A AVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating o in. Futhermore, I authorize the above-named contractor to do the work stated. n i n _ re ner / Applicant / Contractor / Agent Building Dep - rtment Copy December 12, 2017 Date December 12, 2017 1 4 BUILDING PERMIT APPLICATION ❑BUILDING ❑ ELECTRIC Miami Shores Village Building Department 10050 N.E.2nd Avenue, Miami Shores, Florida 33138 Tel: (305) 795-2204 Fax: (305) 756-8972 INSPECTION LINE PHONE NUMBER: (305) 762-4949 Master Permit No. Sub Permit No. RECEIVED DEC 0 4 2017 Fsc 20lt.)1 2-F ROOFING ❑ REVISION ❑ EXTENSION El RENEWAL El PLUMBING ❑ MECHANICAL ❑PUBLIC WORKS ❑ CHANGE OF ❑ CANCELLATION ❑ SHOP CONTRACTOR DRAWINGS JOB ADDRESS: 13 1 Ott Sr City: Miami Shores County: Folio/Parcel#: r1 — 22 2 —93 z nz lv f Miami Dade Zip: 331-=,�3 Is the Building Historically Designated: Yes NO Occupancy Type: Load: Construction Type: Flood Zone: BFE: FFE: OWNER: Name (Fee Simple Titleholder): 3e `V OCSy- Phone#: Address: 13T LI, Nit>q City: S v O [ ) State: FL Zip: aSt3liallT5 Tenant/Lessee�Name: Phone#: 't¢ $53 GO 3, Le Email: ` <'� �<-"U�q• ( t&Ovo-.GCr"-x_ CONTRACTOR: Company Name: C I 16)012;A) 1A Address: ZZ -71•1) St)•S (72 C 9 Phone#: � 2"5( 2.Xq4 City: /1/Ike.,--0 State: /IL, Zip: 33h0 Qualifier Name: (1\64\ ✓ Phone#: 3t)--; Z'fQ 2,('G'1 State Certification or Registration #: CCc--- 13Z -7g/ Certificate of Competency #: DESIGNER: Architect/Engineer: Phone#: Address: City: State: Zip: Value of Work for this Permit: $ Zc/SG Type of Work: ❑ Addition Description of Work: Square/Linear Footage of Work: ❑ Alteration ❑ New c6 Repair/Replace .sem& 7 �fl ❑ Demolition . "•>.i •"y,�y -. �? qtr `"%>j Specifj color of color th iT tele a k� -��1, t a . o;? M , )_ Submittal Fee $ Scanning Fee$ _...m Technology Fee $ Structural Reviews $ (Revised02/24/2014) Permit'Fee $ $`' �Cp CA CCFto/cc Radon Fee $ GO DBPR $ cb Notary $� --- Training/Education Fee $ Double Fee $ Bond $ S00 - O3 TOTAL FEE NOW DUE $ 36 - 50 Bonding Company's -Name (if applicable) Bonding Company's Address City State Zip Mortgage Lender's Name (if applicable) Mortgage Lender's Address City t State Zip Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRIC, PLUMBING, SIGNS, POOLS, FURNACES, BOILERS, HEATERS, TANKS, AIR CONDITIONERS, ETC OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. "WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT." Notice to Applicant: As a condition to the issuance of a building permit with an estimated value exceeding $2500, the applicant must promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person whose property is subject to attachment. Also, a certified copy of the recorded notice of commencement must be posted at the job site for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the inspection will .. t be approved and a reinspection fee will be charged. Signature' OWNER or AGENT The foregoing instrument was acknowledged before me this Lday oft\ , 20 , by .-� , who is rsona to me or who has produced as identification and who did take an oath. NOTARY PUBLIC: Sign: Print: Seal: ************** C6VJSo CANDY CABOVERDE MY COMMISSION # GG 034505 • :.i= EXPIRE : September 28, 2020 • o4av** *PuMIc Underwriters i1,*> 1 i. APPROVED BY (Revised02/24/2014) Signature CONTRACTOR The foregoing instrument was acknowledged before me this 30 day of N pJ _, 20 ''1 , by who isal4c.khown to me or who has produced identification and who did take an oath. NOTARY PUBLIC: as Sign: `. Print: Gey-,�-z Seal: ********************** `Plans Examiner Structural Review r'r;w• •••. CANDY CABOVERDE ' • :4• • MY COMMISSION # CC r,34505 wiy *#*+41,**$P1RF$be6le* 8k*.6'diF***' **** •.No �:;.•• Bonded 'Wu Notary Public Urdarwrners I Zoning Clerk Miami Shores Village Building Department 10050 N.E.2nd Avenue Miami Shores, Florida 33138 Tel: (305) 795.2204 Fax: (305) 756.8972 OWNERS'S AFFIDAVIT OF EXEMPTION ROOF TO WALL CONNECTION HURRICANE MITIGATION RETROFIT FOR EXISTING SITE - BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES PERSUANT TO SECTION 553.844 F.S. To: Miami Shores Village Building Department 10050 NE 2nd Ave Miami Shores, FI 33138 Re: Owner's Name: Skr.46 bey' Date: 1\ I 'L1 )k-1 Property Address: Imo$ Lt kriA��- Roofing Permit Number: Dear Building Official: I t certify that I am not required to retrofit the roof to wall connections of my building because: 'n' he just valuation for the structure for purpose of ad valorem taxation is less than $300,000.00. Please attach proof of ad valorem taxation. ❑ The building was constructed in compliance with the provisions of the Florida Building Code (FBC) or with the provisions of 1994 edition of the South Florida Building Code (1994 SFBC) Signature Print Name State of Florida County of Dade The undersigned, being the first duly sworn, deposes and says that he/she is the owner for the above property mentioned. Sworn to and subscribed before me this 7_.-1 day of p,J t)11 Notary Public, Sate of Florida at Large When the just valuation of the structure for purpose of ad valorem taxation is equal to or more than $300,000.00, and th CANDY CABOVERDE MY COMMISSION # GG 034505 EXPIRES: September 28, 2020 % iSOF not NiMakwaltoriscutwantsectirs SFBC. Then you must provide a building application from a General Contractor for the Roof to Wall connection Hurricane Mitigation. Revised on 5/21/2009 12/4/2017 Property Search Application - Miami -Dade County FFICE QF TNF PROPERTY APPRAISER Property Information Folio: Property Address: Summary Report 11-2232-032-0260 1384 NE 104 ST Miami Shores, FL 33138-2662 Owner Mailing Address PA Primary Zone BEATRICE E GARCIA 1384 NE 104 ST MIAMI SHORES, FL 33138 USA 1100 SGL FAMILY - 2301-2500 SQ Primary Land Use Beds / Baths / Half 0101 RESIDENTIAL - SINGLE FAMILY : 1 UNIT 3/2/1 Floors 2 Living Units 1 Actual Area Living Area Sq.Ft Sq.Ft Adjusted Area Lot Size Year Built 2,747 Sq.Ft 8,850 Sq.Ft 1956 Assessment Information Previous Sale Year 2017 2016 2015 Land Value 30297-0235 $309,729 $270,112 Building Value C,729 ,191 $191,191 $191,191 XF Value ,201 $1,215 $984 Market Value rAssessed .. 12,120 $502,135 $462,287 Value $191,515 $187,576 $186,273 Benefits Information Benefit Save Our Homes Cap Homestead Type Assessment Reduction Exemption 2017 2016 2015 $310,605 $314,559 $276,014 $25,000 $25,000 $25,000 Second Homestead Exemption $25,000 $25,000 $25,000 Note: Not all benefits are applicable to all Taxab e Values (i.e. County, School Board, City, Regional). Short Legal Description 32 52 42 RIVER BAY PARK ADDN PB 40-72 LOT 5 BLK 4 LOT SIZE 75.000 X 118 OR 15921-3279 0593 1 Generated On : 12/4/2017 Taxable Value Information 20171 County 20161 2015 Exemption Value $50,000 $50,000 $50,000 Taxable Value $141,515 $137,576 $136,273 School Board Exemption Value $25,000 $25,000 $25,000 Taxable Value $166,515 $162,576 $161,273 City Exemption Value Taxable Value $50,000 $141,515 $50,000 $137,576 $50,000 $136,273 Regional Exemption Value $50,000 $50,000 $50,000 Taxable Value $141,515 $137,576 $136,273 Sales Information Previous Sale Price OR Book - Page Qualification Description 09/12/2016 $100 30297-0235 Corrective, tax or QCD; min consideration 05/01/1993 $181,000 15921-3279 Sales which are qualified 11/01/1989 $160,000 14346-3469 Sales which are qualified The Office of the Property Appraiser is continually editing and updating the tax roll. This website may not reflect the most current information on record. The Property Appraiser and Miami -Dade County assumes no liability, see full disclaimer and User Agreement at http://www.miamidade.gov/info/disclaimer.asp Version: Section A B Master Permit No: Contractor's Name: JobAddress: Miami -Dade County HVHZ Electronic Root -Pe Section A (General. Information) Process No: [CITY ROOFING /JIY NC /Dy s� • Low Slope O Asphaltic Shingles ❑ Sprayed Polyurethane Foam Roof Category O Mechanically Fastened Tile ❑ Metal Panel/Shingles ❑ Other: Roof Type ❑,. Mortar/Adhesive Set Tile O Wood Shingles/Shakes . . •• . .. . .. . • . . . • 0 New Roof l Re -Roofing 0 Recovering 0 Repair 0 Maintenaw,,,, •. •,• •• Are there Gas Vent Stacks located on the roof? 0 Yes 0 No If yes, what type?•.ri'Natural• ; LPGX • Roof System Information Low slope roof area (ft.2) Steep Sloped area (ft.2) 26-b0 Section B (Roof Plan) .•.. . . . Total (ft.2) I •4‘,.. .... . . . . . .' . .� . ' Sketch Roof Plan: Illustrate all levels and sections, roof drains, scuppers, overflow scuppers and oberflotiv draiitSaQclpde • dimensions of sections and levels, clearly identify dimensions of+elevated pressure zones and location of parapets. • • Perimeter Width (a): Corner Size (a' x a): RECEIVED 4S DEC 0 41017 CIA Is.% • • • 1 Tile Roof System Roof System Manufacturer: Miami -Dade County HVHZ Electronic Roof Permit Form Section D Tile Roof System !EAGLE TILE PRODUCTS Notice of Acceptance Number (NOA): 16-0314.06 Minimum Design Wind Pressures, If Applicable (from RAS 127 or Calculations): P1: 39.1 P 2: 68.1 P 3: 100.7 Maximum Design Wind Pressures, (From the NOA Specific system): i4U•4 psf Fill in the specific roof assembly components. If a component is not required, insert not applicable (n/a) in the text box. Roof Slope: 4 Roof Mean Height: "/12" 10 Method of Tile Attachment: ft. I --Adhesive, Medium Paddy Polyfoam Polypro-fj Alternate Method of Tile Attachment per NOA: IN/A Drip Edge Size & Gauge: Drip Edge Material Type: Drip Edge Fastener Type: --3" face 26 ga.-- --Galvinized Metal -- 1.25" RING SHANK Hook Strip/Cleat gauge or weight: -- Select Hook Strip -- Deck Type: 1--5/8" Plywood-- - Optional Insulation: IN/A . . . .. . .. . • • • • • • • Optional Nailable Substratti • N/A Optional Nailable Substratc:AttArhent: IN/A .. Basesheet Type: t)N, 26- Fastener 6 Fastener Type for Basesheet Attachment: 1.25" RING SHANK AND 5/8" TIN CAP Tile Underlayment (Cap Sheet ) Type: I ()Su 3cQ Tile Underlayment Attachment Method: SELF -ADHERED Tile Profile: Section E tl' Miami=Dade County HVHZ Electronic Roof Permit Form Section E (Tile Calculations) Method 1 "Moment Based Tile Calculations Per RAS 127" For Moment based tile systems, use Method 1. Compare the values for Mr with the values from Mf. If the Mf values ale greater than or equal to the Mr values, for each area of the roof, then the tile attachment method is acceptable. P 1: 39.1 xX P2:68.1 x P 3: 100.7 .278 47771 - Mg: =1787371. Mg: 7.59' = 28.00 - Mg:7.59 = Mr3: 7.59 = Mr1: 11.35 20.41 140.4 Method 3 "Uplift Based Tile Calculations PerRAS 127" NOA Mf NOA Mf NOA Mf. • • • • • • • • • •• • •. • • • • • • • .. • For Uplift based tile system's use Method 3. Compare the values for F' with the values for Fr: If the F' values are greatet•ttharf 5i equal to the'Fr values, iti ...: each area of the roof, then the tile°attachment method is acceptable'. •••• • • • • • • • • • • •••• ••.• 'er-1'• (MA F' • • P1: n x P2: P3: xl: x1: x w: =1 Ixw:I 1= =1 IXW: W: 11111 x cos 8:[ = Fr1: cos'9: fl = Fr2: xcos 9:I = Fr3: • • Whereto Obtain Information to complete tile calculations • • • AIO,AU • ••• • < NOAH • • • Description Symbol Where to Find Design Pressure P1 or P2 or P3 Table 1 RAS 127, or by an engineer analysis prepared, signed and sealed by a professional engineer based on ASCE 7: Mean Roof Height H Job Site Roof Slope a Job Site Aerodynamic Multiplier X Product Approval (NOA) Restoring Moment due to Gravity Mg Product Approval (NOA) Attachment Resistance Mf Product Approval (NOA) Required Moment. Resistance Mr Calculated Minimum Attachment Resistance F' Product Approval (NOA) Required Uplift Resistance Fr Calculated Average Tile Weight W Product Approval (NOA) Tile Dimensions I = length w = width Product Approval (NOA) • DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) BOARD AND CODE ADMINISTRATION DIVISION NOTICE OF ACCEPTANCE (NOA) Eagle Roofing Products LLC 1575 East`C.R. 470 Sumterville, FL 33585 MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 Miami, Florida 33175-2474 T (786) 315-2590 F (786) 315-2599 www.mamidadcgov/economy SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miami -Dade County RER -Product Control Section to be used in Miami -Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ). This NOA shall not be'valid after the expiration date stated below. The Miami -Dade County Produit.Connie Ce;tiion (in Miami -Dade County) and/or the AHJ (in areas other than Miami -Dade County) reserve' the rigtit:o haus £his • product or material tested for quality assurance purposes. If this product or material fails to pQripr, in the $cc'hpled manner, the manufacturer will incur the expense of such testing and the AHJ may immediatelyteleke, modify,.or suspend the use of such product or material within their jurisdiction. RER reserves the right ;revoke this a Ee ptance, • • if it determined by Miami -Dade County Product Control Section that this product or materiarfalis to meettittc• requirements of the applicable building code. . . • ••• • This product is approved as described herein, and has been designed to comply with the Floriu lding Cede' • • • • • including the High Velocity Hurricane Zone of the Florida Building Code. •• • •• DESCRIPTION: Bel Air, Bel Air Double Eagle,: Ponderosa, Ponderosa Double Eagle, C'so•1deri Eagle' R • • Low Profile Concrete Tiles • • LABELING: Each unit shall bear a pernianent'label with the manufacturer's name or logo, city, state and following statement: "Miami -Dade County Product Control. Approved", unless otherwise noted herein. RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building codenegatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by'the words Miami -Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of f the NOA'is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or"its distributors and shall be available for inspection at the job site at the request of the Building Official. This NOA renews NOA•No.15-0223.18 and consists of pages 1 through 9. The submitted documentation was reviewed by Gaspar J Rodriguez. MANMADE courrr I APPROVED NOA No.:16-0314.06 Expiration Date: 10/05/21 Approval Date: 06/16/16 Page 1 of 9 • •• • • i ROOFING ASSEMBLY APPROVAL Category: Sub Category: Material: Roofing Roofing Tiles Concrete 1. SCOPE: This approves a new rooting system using "Low Profile Concrete Tile" as manufactured by Eagle Roofing Products LLC in Sumterville, FL and described in Section 2 of this Notice of Acceptance. For use in locations where the pressure requirements, as determined by applicable Building Code, do not exceed the design pressure values obtained by calculations in compliance with RAS 127 using the values listed in section 4 herein. The attachment calculations shall be done as a moment based system. 2. PRODUCT DESCRIPTION: Manufactured by Applicant • • Test Products Dimensions Specifications Description • • • •• • TAS 112 Flat profile concretero13114e equipped With two Type 3a nail holes. For adhesive ryeIvairect dell Class III battened nail -on applica.• • • • • • • ..•. Lenght = 17" TAS 112 Flat profile concrete mottle equippeiiavith two Width = 12 %a" Type 3a nail holes. For adhesinstptirect deckor Thickness = Class III battened nail -on applications! • • Bel Air Lenght = 17" Concrete Tile Width = 12'/a" Thickness ='/z" Bel Air Double Eagle Concrete Tile Ponderosa Concrete Tile Ponderosa Double Eagle Concrete Tile Golden Eagle Concrete Tile Trim Pieces r• .-1"7-17,97-4-477-•—. . .r•� .. 1. APNC4E3 Lenght = 17" TAS 112 Width =12 I/a" Type 3a Thickness ='/z" Class III Lenght = 17" TAS 112 Width = 12'/" Type 3a Thickness ='/z" Class III Lenght = 17" TAS 112 Width =121/" Type 3a Thickness = %z" Class III Lenght = varies TAS 112 Width = varies varying thickness • • • • • Flat profile concrete roo'itile.vith shatergash equipped with two nail holes. For adhesive set, direct deck or battened nail -on applications. Flat profile concrete roof tile with shake finish equipped with two nail holes. For adhesive set, direct deck or battened nail -on applications. Flat profile concrete roof tile brushed finish equipped with two nail holes. For adhesive set, direct deck or battened nail -on applications. Accessory trim, clay roof pieces for use at hips, rakes, ridges and valley terminations. Manufactured for each tile profile. NOA No.:16.0314.06 Expiration Date: 10/05/21 Approval Date: 06/16/16 Page 2 of 9 2.1 EVIDENCE SUBMITTED: Test Agency PRI Asphalt Technologies Redland Technologies Redland Technologies Redland Technologies Redland Technologies Redland. Technologies Redland Technologies The Center for Applied Engineering, Inc. The Center for Applied Engineering, Inc. The Center for Applied Engineering, Inc. The Center for Applied Engineering, Inc. The Center for Applied Engineering, Inc. The Center for Applied Engineering, Inc. The Center for Applied Engineering, Inc. Celotex Corporation Testing Service Celotex Corporation Testing Service Walker Engineering, Inc. Walker Engineering, Inc. ATL of South Florida PGAMORDE COUNTY Test Identifier ERPF -001-02-01 7161-03 Appendix III 7161-03 Appendix 111 7161-03 Appendix 1I P0402 Letter Dated Aug. 1, 1994 P09647-01 94-084 25-7094-(2, 5, & 8) 25-7183-(5 thru 6) 25-7214-(1, 5 , & 8) 25-7487-2 25-7496-(1 & 4) 25-7804-6 520109-1 520111-4 520191-1 Calculations Calculations RT1214.01-15 Test Name/Report TAS 112 Static Uplift Testing TAS 102 Static Uplift Testing TAS 102(A) Wind Tunnel Testing TAS 108 (Nail -On) Withdrawal Resistance Testing of screw vs. smqoth shank nails Wind Tunnel Testing TAS 108 (Nail -On) Wind Tunnel Testing TAS 108 (Mortar Set) Static Uplift Testing TAS 101 (Mortar Set) Static Uplift Testing TAS 102 Static Uplift Testing TAS 102 Static Uplift Testing TAS 102 Static Uplift Testing TAS 102 Static Uplift Testing TAS 102 Static Uplift Testing TAS 102 Static Uplift Testing TAS 101 Static Uplift Testing TAS 101 Aerodynamic Multiplier Restoring Moments Due to Gravity TAS -112 .. . .... .... • • .. .. •. • . . • • •. . . Date Aug. 2006 Dec. 1991 Dec. 1991 Dec. 1991 Sept. 1993 Aug. 1994 'Aug. 1994 .. . • •• • May 1994 . . • . . .... . •• Oct' 1994 • • .... . .... Felx 1995 11ch, 1995 Dec. 1995 Dec. 1995 Sep. 1996 Dec. 1998 March 1999 Sep. 2006 Sep. 2006 12/17/15 NOA No.:16-0314.06 Expiration Date: 10/05/21 Approval Date: 06/16/16 Page 3 of 9 • • . . . 3 LIMITATIONS: 3.1 Fire classification is not part of this acceptance. 3.2 For mortar or adhesive set tile applications, a static field uplift test in accordance with TAS 106 shall be required, refer to applicable Building Code. 3.3 Applicant shall retain the services of a Miami -Dade County Certified Laboratory to perform quarterly test in accordance with TAS 112, appendix 'A'. Such testing shall be submitted to the Miami -Dade County Product Control Section for review. 3.4 Minimum underlayment shall be in compliance with the applicable Roofing Applications Standards listed section 4.1 herein, 3.5 30/90 hot mopped underlayment applications may be installed perpendicular to the roof slope unless stated otherwise by the underlayment material manufacturers published literature. 3.6 This acceptance is for wood deck applications. Minimum deck requirements shall be in compliance with applicable Building Code, 4 INSTALLATION: • • •.••.. 4.1 Eagle Roofing Products LLC Bel Air, Bel Air Double Eagle, Ponderosa, Golden Eagle; Posaarosa 1louble Eagle Flat Concrete Roof Tiles and its components shall be installed in strict compliance with RoofingiApvt.ation Standard RAS 118, RAS 119 and RAS 120, 4.2 Data For Attachment Calculations • • • • • • • .... • • • • • • • • • Table 1: Average Weight (W) and Dimensions (I x w) •••• • Tile Profile Weight -W (Ibf) Length-) ( ►,• Width; -w (ft) Bel Air, Bel Air Double Eagle, Ponderosa, Golden Eagle, Ponderosa Double Eagle Flat Tile 11.4 1.42 •••. • • .. • .•• • .. Table 2: Aerodynamic Multipliers - A (ft3) -- Tile Profile A (ft3) A (ft3) 5":12" Batten Application Direct Deck Application Bel Air, Bel Air Double Eagle, Ponderosa, Golden 0.301 0.278 Eagle, Ponderosa Double Eagle Flat Tile Direct Deck Battens Table 3: Restoring Moments due to Gravity - M9 (ft-lbf) Tile Profile 3":12" 4":12" 5":12" 6":12" Greater than 7":12" Bel Air, Bel Air Double Eagle, Ponderosa, Golden Eagle, Ponderosa Double Eagle Fiat Tile Battens Direct Deck Battens Direct Deck Battens Direct Deck Battens Direct Deck Battens Direct Deck 7.48 7.71 7.37 7.59 7.22 7.44 7.05 7.27 6.86 7.07 -. -,-- A?r�OVE7 NOA No.:16-0314.06 Expiration Date: 10/05/21 Approval Date: 06/16/16 Page 4 of 9 • • ..•• .• • • • Table 4: Attachment Resistance Expressed as a Moment - Mf (ft-Ibf) for Nail -On Systems Tile Profile Fastener Type Direct Deck (min 15/32" plywood) Direct Deck (min. 19/32" plywood) Battens Bel Air, Bel Air Double Eagle, Ponderosa, Golden Eagle, Ponderosa Double Eagle Flat Tile 2-10d Ring Shank Nails 30.9 38.1 17.2. 1-10d Smooth or Screw Shank Nail 7.3 9.8 4.9 2-10d Smooth or Screw Shank Nails 14.0 18.8 7.4 1 #8 Screw 30.8 30.8 18.2 2 #8 Screw 51.7 51.7 24.4 1-10d Smooth or Screw Shank Nail (Field Clip) 24.3 24.3 24.2 1-10d Smooth or Screw Shank Nail (Eave Clip) 19.0 19.0 22.1 2-1 Od Smooth or Screw Shank Nails (Field Clip) 35.5 35.5 •- •• • • 348 • 2-10d Smooth or Screw Shank Nails (Eave Clip) 31.9 31.9 '' • :•32.2. • • . 2-10d Ring Shank Nails' 50.3 65.5 ••---• • •-4> . 1. Installation with a 4" tile headcap and fasteners are located a min. of 2W from head Af tile. .... • Table 5: Attachment Resistance Expressed as a Moment Mf Man. .. for Two Patty Adhesive Set Systems • • at Tile Profile Tile Application . Ahaeliment tesistance Bel Air, Bel Alr Double Eagle, Ponderosa, Golden Eagle, Ponderosa Double Eagle Flat Tile Adhesive' 31.32 • • i, 1 See manufactures component approval for installation requirements. 2 The Dow Chemical Company TileBond Average weight per patty 13.9 grams. ICP Adhesives Polyset® AH -160 Average weight per patty 8 grams. Table 6: Attachment Resistance Expressed 'as a Moment - Mf (ft-Ibf) for Single Patty Adhesive Set Systems Tile Profile Tile Application Attachment Resistance Bel Air, Bel Air Double Eagle, Ponderosa, Golden Eagle, Ponderosa Double Eagle Flat Tile ICP Adhesives Polyset® AH -160 118.93 ICP Adhesives Polyset® AH -160 40.44 3 Large paddy placement of 45 grams of PolyProTM. 4 Medium paddy placement of 24 grams of PolyProTM. Table 7: Attachment Resistance Expressed as a Moment - Mf(ft-Ibf) for Mortar Set Systems Tile Profile Tile Application Attachment Resistance Bel Air, Bel Air Double Eagle, Ponderosa, Golden Eagle, Ponderosa Double Eagle Flat Tile Mortar Sets 43.9 5 Tile-Tite Roof Tile Mortar. 14AMICIALIE cowry NOA No.:16-0314.06 Expiration Date: 10/05/21 Approval Date: 06/16/16 Page 5 of 9 • • • • •••• • • ••. • •• • • 5. LABELING : All tiles shall bear the imprint or identifiable marking of the manufacturer's name or logo (See Detail Below), or following statement: "Miami -Dade County Product Control Approved". EAiiL" FLORIDA (LOCATED ON UNDERSIDE OF TILE) OR EAGLE FL (LOCATED ON FRONTSIDE OF TILE) .• • ••. • •• • •• • • • • • • • •• • - • - . • •..• .... • • • • - •••• ..•. . . • .•• • •..• •••• •, • • •• • • • • • •• • • .. •. • •.. • • • .• BEL AIR, BEL AIR DOUBLE EAGLE, PONDEROSA, GOLDEN EAGLE, PONDEROSA DOUBLE EAGLE CONCRETE ROOF TILE LABEL, SUMTERVILLE PLANT 6. BUILDING PERMIT REQUIREMENTS: 6.1 Application for building permit shall be accompanied by copies of the following: 6.1.1 This Notice of Acceptance. 6.1.2 Any other documents required by AHJ or applicable Building Code in order to properly evaluate the installation of this system. NOA No.:16-0314.06 Expiration Date: 10/05/21 Approval Date: 06/16/16 Page 6 of 9 PROFILE DRAWING BEL AIR • . •• • • • •• • •• • • • • • • • •• • • • . •••• •••• • • • • • • •••• •••• • • •••• • • • •• •• •••• • • • • • • • • • • • BEL AIR DOUBLE EAGLE MAMICADE COUNTYT• • • • ••• • • • NOA No.:16-0314.06 Expiration Date: 10/05/21 Approval Date: 06/16/16 Page 7 of 9 PONDEROSA • • • • •• • • • • •• • • • • • •• • • •••• •••'• . • • • • • • •••• • • •• •• • • • • • • • • • • •• • PONDEROSA DOUBLE EAGLE MANMADE COUNTY •••• •••• • •••• • • • • • • • • • • • ••• • • • NOA No.:16-0314.06 Expiration Date: 10/05/21 Approval Date: 06/16/16 Page 8 of 9 GOLDEN EAGLE END OF THIS ACCEPTANCE • • • • • • •• • •. • • • • •• •• . • • • • •••• •••• . • • • • •.•• •••• •••• • • • •• •• •••• • • • • • • • • • • • • • • • • • • • • .• • ••. • • • NOA No.:16-0314.06 Expiration Date: 10/05/21 Approval Date: 06/16/16 Page 9 of 9 MIAMI COUff Y DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) BOARD AND CODE ADMINISTRATION DIVISION NOTICE OF ACCEPTANCE (NOA) Interwrap, Inc. 32923 Mission Way Mission, BC, Canada V2V-6E4 MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 Miami, Florida 33175-2474 T (786)315-2590 F (786) 315-2599 www.miamidade.eov/economv SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ). This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product or material tested for quality assurance purposes. If this product or material fails to perfolm in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ .may ir$fittitItely revoke, modify, or suspend the use of such product or material within their jurisdiction. RRRJeserves the right to . • revoke this acceptance, if it is determined by Miami -Dade County Product Control Sectiexrthet this prod • material fails to meet the requirements of the applicable building code. • .••• .••• This product is approved as described herein, and has been designed to comply with the F1oric►a tuilding•.o e. including the High Velocity Hurricane Zone of the Florida Building Code.• •• •• •• •• •.1•• • DESCRIPTION: Titanium® UDL-30 / Titanium® PSU-30, Titanium® UDL-25 PLUS / Titaniu4* MU -30, and UDL-MD (2 ply) / Titanium® PSU-30 Underlayment System : . . • :• • • • • • • • • • •.• • • LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein. • RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This NOA renews and revises NOA# 13-0730.01 and consists of pages 1 through 7. The submitted documentation was reviewed by Alex Tigera. MIAMI•DADE COUNTY APPROVED NOA No.: 14-0603.19 Expiration Date: 01/26/22 Approval Date: 02/02/17 Page 1 of 7 • ROOFING COMPONENT APPROVAL Category: Sub -Category: Material: Roofing Underlayment Polypropylene TRADE NAMES OF PRODUCTS MANUFACTURED BY APPLICANT TABLE 1 Product Dimensions Titanium® UDL-25 PLUS Manufacturing Location #1& #2 UDL-MD (2Ply system) Manufacturing Location #2 Titanium® UDL-30 Manufacturing Location #1& #2 Titanium® PSU-30 Manufacturing Location #3 48" x 250' rolls 48" x 250' rolls 48" x 250' rolls 36" x 72' rolls MANUFACTURING LOCATIONS: 1. ML l 2. ML3 3. ML4 MIAMI•DADE COUNTY APPROVED Test Specification ASTM D226 Type I & II ASTM D226 Type I & II ASTM D226 Type I & II TAS 103 Product Description Woven synthetic polymer underlayment with one side coated with UV protected and slip resistant polymer stabilized polypropylene on both sides. Woven synthetic polymer underlayment with a chemical slip resistant gnd Lly protected coating • •• • both sides. • • • .• • Woven synthetic polynnernNerlayirerit with two sides coated with UV pi -Welted and Aril tesistant•;••. polymer stabilized polyprongene on lk?i?i sides. • Unreinforced polymer modified bitrpgp,paterial adhered to the underside of Lpolynttr-coated, • synthetic woven sheet. The undersitte ie liacked' with a release film. • • NOA No.: 14-0603.19 Expiration Date: 01/26/22 Approval Date: 02/02/17 Page 2 of 7 • EVIDENCE SUBMITTED: Test Agency Test Identifier Test Name/Report Date Intertek Testing Services #3031783 TAS 104 02/19/03 3124826-01 ASTM E108 02/19/08 3119607C0Q-003B ICC -ES AC48 02/20/08 3130639C0Q-002A ASTM D226 02/20/08 3124826MID-007 ASTM E108 02/25/08 3146738C0Q-003B ASTM D 1876/ TAS 117 03/28/08 3146738C0Q-003A ASTM D226 04/22/08 Trinity 1 ERD I35520.06.11 TAS 103 / TAS 104 06/15/11 I35520.06.11 TAS 103 / TAS 104 06/15/11 I38010.08.11 ASTM D226 08/11/11 I35520.08.11-1 TAS 114 08/12/11 I35520.08.11 ASTM D2523 / D1781 08/17/11 I44970.07.13 -R1 ASTM D226, AST131876 ; • •69 jv1 D/09/13 and TAS 114(G)• : .•. .• . • • . . . .... .... . . • . . •••• .... . . . . • . .. .. •••• • • • • • • • • •• • • •• • ••• • • • NOA No.: 14-0603.19 Expiration Date: 01/26/22 Approval Date: 02/02/17 Page 3 of 7 APPROVED TITANIUM UNDERLAYMENT SYSTEM ASSEMBLIES: Deck Type 1: Wood Deck Description: 19/32" or greater plywood or wood plank System E(1): Base sheet mechanically fastened to deck, subsequent cap membrane self- adhered. All General and System Limitations shall apply. Base sheet: One or more plies of Titanium® UDL-25 PLUS or Titanium® UDL-30 applied with minimum 4" horizontal laps and minimum 6" vertical laps and mechanically fastened as noted below. Note: Titanium® UDL-30 shall be inverted to provide a smooth bonding surface. Primer is not required when Titanium® UDL-30 is installed inverted (printed side facing down) Fastening: Primer: Ply Sheet: Membrane: Surfacing: Note: MIAMI•DADE COUNTY APPROVED Miami -Dade approved nails & metal/tin caps spaced 6" o.c. at the 4" horizontal laps and 8" o.c. in a grid pattern having three, equally spaced, staggered row: in the. field "MA; sheet. .11 Metal/Tin caps shall be primed with ASTM D41 primer • ' (Optional) Titanium® PSU-30, self -adhered with minimum 3" hor••• Qgtal lapsgJ ptinimu • 6" vertical laps. .... ' • Titanium® PSU-30, self -adhered, with minimum 3" horizontal lapsziminimum 6" vertical laps. Place the first course of Titanium® PSU-30 parallel to tht eave%ti,415g1d, using a heavy pressure roller under safe conditions to further secure th'er•mem1 rane.• Approved for asphalt shingle, mechanically fastened roof tile, foam -on roof tile, metal roofing, wood shakes & shingles or slate roof assemblies. . . For tile roof assemblies, refer to RAS 118, 119 or 120 and the tile manufacturer's NOA. For foam -on tile roof assemblies, approved use with ICP Adhesives Polyset AH -160 and Dow TILE BOND Roof Tile Adhesive. NOA No.: 14-0603.19 Expiration Date: 01/26/22 Approval Date: 02/02/17 Page 4 of 7 Deck Type 1: Wood Deck Description: 19/3211 or greater plywood or wood plank System E (2): Base sheet mechanically fastened to deck, subsequent cap membrane self- adhered. All General and System Limitations shall apply. Base sheet: One or more plies Titanium® UDL-30 applied with minimum 4" horizontal laps and minimum 6" vertical laps and mechanically fastened as noted below. Fastening: Miami -Dade approved nails & metal/tin caps spaced 6" o.c. at the 4" horizontal laps and 8" o.c. in a grid pattern having three, equally spaced, staggered rows in the field of the sheet. Primer: Titanium® UDL-30 shall be primed on the printed side with ASTM D41 primer prior to placement of cap sheet. Ply Sheet: (Optional) Titanium® PSU-30, self -adhered, with minimum 3" horizontal lapcadreinimum 6" vertical laps.' •• •• •• • • .• • • • •• •• Membrane: Titanium® PSU-30, self -adhered, with minimum 3" horizontal laps. inklminimum 6" • .• • • vertical laps. Place the first course of Titanium® PSU-30 paralle.l•to•til eave4 dein a heavy • pressure roller under safe conditions to further secure the membraMMC' • •••• • • • • Surfacing: Approved for asphalt shingle, mechanically fastened roof tile, foam -on roof tile,'metal• • roofing, wood shakes & shingles or slate roof assemblies. • •• •••• • • •• • • Note: For tile roof assemblies, refer to RAS 118, 119 or 120 and the tilefxannfactun+es'.s NOA. Jor • foam -on tile roof assemblies, approved use with ICP Adhesives Polyset AH -160 am; Dow TILE BOND Roof Tile Adhesive. MIAMI•DADE COUNTY APPROVED NOA No.: 14-0603.19 Expiration Date: 01/26/22 Approval Date: 02/02/17 Page 5 of 7 Deck Type 1: Wood Deck Description: 19/32" or greater plywood or wood plank System E(3): Base sheet mechanically fastened to deck, subsequent cap membrane self- adhered. All General and System Limitations shall apply. Base sheet: One or more plies of UDL-MD (2Ply system) applied with minimum 4" horizontal laps and minimum 6" vertical laps and mechanically fastened as noted below. Fastening: Miami -Dade approved nails & metal/tin caps spaced 6" o.c. at the 4" horizontal laps and 8" o.c. in a grid pattern having three, equally spaced, staggered rows in the field of the sheet. Ply Sheet: (Optional) Titanium® PSU-30, self -adhered with minimum 3" horizontal laps and minimum 6" vertical laps. Membrane: Titanium® PSU-30, self -adhered, with minimum 3" horizontal laps and minigium ¢" vertical laps. Place the first course of Titanium® PSU-30 parallel to the eaveald field, using a heavy pressure roller under safe conditions to further sector. Thal memane. •• • o • • •• • Surfacing: Approved for asphalt shingle, mechanically fastened roof tile, fodbf-bfi roof tile, tiietal Note: MIAMI•DADE COUNTY APPROVED roofing, •wood shakes & shingles or slate roof assemblies. • • • • •• •• •' • •••• •••• • • For tile roof assemblies, refer to RAS 118, 119 or 120 and the tilt rfigudfactur ;4,NOA. $4r... foam -on tile roof assemblies, approved use with ICP Adhesives Rolys€ AH -160 and Dow •• TILE BOND Roof Tile Adhesive. • •• • • • • • •• • ••• • • • NOA No.: 14-0603.19 Expiration Date: 01/26/22 Approval Date: 02/02/17 Page 6 of 7 BUILDING PERMIT REQUIREMENTS Application for building permit shall be accompanied by copies of the following: 1. This Notice of Acceptance. 2. Any other documents required by the Building Official or applicable building code in order to properly evaluate the installation of this material. LIMITATIONS 1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials Directory for fire ratings of this product. 2. This acceptance is for prepared roofing applications. Minimum deck requirements shall be in compliance with applicable building code. 3. Titanium Synthetic Underlayments shall be applied to a smooth, clean and dry surface with deck free of irregularities. All nails in the deck shall be carefully checked for protruding heads. Re -fasten any loose decking panels. Sweep the deck thoroughly to remove any dust and debris prior to application. 4. Titanium® UDL-25 PLUS / Titanium® PSU-30, Titanium® UDL-30 / Titanium PSU-30, tJ9L•T1VID (211%,••• system) / Titanium® PSU-30 two-ply underlayment system, may be used in assa?t :hing14, mechanically • fastened roof tile, foam -on roof tile, metal roofing, wood shakes & shingles or slate/reef essembtes • • ` 5. The standard "maximum roof pitch for the Titanium® UDL-25 PLUS / Titanium® P31!J'1&, Titaniurf® UDL3O • / Titanium® PSU-30, UDL-MD (2Ply system) / Titanium® PSU-30 two-ply underlMfeht syste 110111 be 5'12 • for flat tiles and 6:12 on profiled tiles with lugs. For flat tile applications at slopes exceeding tnflat tiler `• shall be staged 2 base tiles perpendicular to slope behind a mechanically attachgsi•tlaetten or •tp;•board wj • • • maximum 7 tiles high on the slope atop base tiles (Total of stack not to exceed 9 tik,s,). At roof slgpes greater . • than the above limitations, the use of loading battens or toe boards are required to load the:roof tile. • ' 6. Titanium Synthetic Underlayments shall not be applied over an existing roof memb;an .c a recever system. • • 7. Titanium® UDL-30 / Titanium® PSU-30, Titanium® UDL-25 PLUS / Titanium® PSU-30, UDL'1l4P:2Ply • system) / Titanium® PSU-30 two-ply underlayment system shall not be left exposed as a temporary rEEf for longer than 90 days of application. 8. Titanium Synthetic Underlayments are components used in roof system assemblies. Roof system assemblies are approved under a specific Notice of Acceptance. Refer to Prepared Roofing System Product Control Notice of Acceptance for listed approval of this product with specific prepared roofing products. 9. Titanium Synthetic Underlayments may be used with any approved roof covering Notice of Acceptance listing Titanium Synthetic Underlayments as a component part of an assembly in the Notice of Acceptance. If Titanium Synthetic Underlayments are not listed, a request may be made to the Authority Having Jurisdiction (AHJ) or the Miami -Dade County Product Control Department for approval provided that appropriate documentation is provided to detail compatibility of the products, wind uplift resistance, and fire testing results. 10. All membranes or packaging shall bear the imprint or identifiable marking of the manufacturer's name or logo and the following statement: "Miami -Dade County Product Control Approved" or the Miami -Dade County Product Control Seal as shown below. MIAMI•DADE COUNTY APPROVED END OF THIS ACCEPTANCE MIAMI•DADE COUNTY APPROVED NOA No.: 14-0603.19 Expiration Date: 01/26/22 Approval Date: 02/02/17 Page 7 of 7 • "Delivering Excellence Every Day" MIAMI-DADE COUNTY REQUIRED OWNERS NOTIFICATION FOR ROOFING CONSIDERATIONS It is the responsibility of the roofing contractor to provide the owner with the required roofing permit, and to explain to the owner the content of this form. The owner's initials in the designated space indicates that the item has been explained. 1. Aesthetics -workmanship: The workmanship provisions of Chapter 15 (High Velocity Hurricane Zone Tare for the purpose of providing that the roofing system meets the wind resistance and water intrusion performance standards. Aesthetics (appearance) are not a consideration with respect to workmanship provisions. Aesthetic issues such as color or architectural appearance, that are not part of a zoning code, should be addressed as part of the agreement between the owner and the contractor. 2. Renailing wood decks: When replacing roofing, the existing wood roof deck may have to be rena d in accordance with the current provisions of Chapter 16 (High Velocity Hurricane Zorml vi the Florida Building Code. (The roof deck is usually concealed prior to removing the existing rioof gystem> •. • . . 3. Common roofs: Common roofs are those which have no visible delineljgi• ietween; eighbofiing unit i.e. townhouses, condominiums, etc.). In buildings with common roofs, the roofing contraotor and/af owner should notify the occupants of adjacent units of roofing work to be performed."" •••• Ira 4. Exposed ceilings: Exposed, open beam ceilings are where the undersidVof the roof $tcking• Lfifi � vie 11- d from below. The owner may wish to maintain the architectural appearance;:thdrefore, roofing nail • penetrations of the underside of the decking may not be acceptable. The owner protdeethe option of • maintaining this appearance. • • • 5. Ponding water: The current roof system and/or deck of the building may not drain well and may c . u ! water to pond (accumulate) in low-lying areas of the roof. Ponding can be an indication of structural distress and may require the review of a professional structural engineer. Ponding may shorten the life expectancy and performance of the new roofing system. Ponding conditions may not be evident until the original roofing`system is removed. Ponding conditions should be corrected. . 6. Overflow scuppers (wall outlets): It is required that rainwater flow off so that the roof is not ove l oaded from a build up of water. Perimeter/edge walls or other roof extensions may block this discharge if overflow scuppers (wall outlets) are not provided. It may be necessary to install overflow scuppers in accordance with the requirements of: Chapter 15 and 16 herein and the Florida Building Code, Plumbing. 7. Ventilation: Most roof structures should have some ability to vent natural airflow through the i to or of the structural assembly (the building itself). The existing amount of attic ventilation shall not be reduced. Owner's/Agent's Signature: Contractor's Signature: f Property Address: 384 /i- Date: Permit Number: