RF-17-2305ENGINEERING ederal & TESTING INC. 250 SW 13th Ave Pompano Beach, FL 33069 Dated: Friday, November 24, 2017 Paul Bange Roofing 7000 SW 21st Place Davie, Florida 33317 RE: TAS -106 Tile Uplift Test Proposed Roof: Bach Residence Permit #(RF -9-17-2305) 9304 NE 5th Avenue Miami Shores, FL 33138 Phone 954-784-2941 800-848-1919 Fax 954-784-7875 fed-eng.com Order Number 17-PBR-369 In accordance with your authorization, Federal Engineering & Testing, Inc. has performed Tile Uplift Testing in compliance with Testing Application Standards TAS -106 and the Florida Building Code High Velocity Hurricane Zone on November 22, 2017 at the above referenced project. The purpose of our inspection was to determine the uplift capacity of the roof tiles for the residence at the above referenced project. The subject roof consisted of S -Shaped Concrete Tile Foam Set. The pitch of the subject roof is 4/12. Our field engineer visited the site and conducted 3 uplift tests on the roof tiles. All tests were performed according to the Florida Building Code High Velocity Hurricane Zone and protocol TAS -106 using an Intercomp Scale Model CS200. The following is a summary of results: Field Test Results Test Number Test Location Field Uplift Pull Test Test Results N/A Corner See Attached Diagram 35 ± 5 Pounds N/A 1 Perimeter See Attached Diagram 35 ± 5 Pounds Passed 2 Field See Attached Diagram 35 ± 5 Pounds Passed 3 Hip/ Ridge See Attached Diagram 35 ± 5 Pounds Passed All test results were found to be in compliance with TAS -106 and the Florida Building Code The test results are limited to the tested areas. If other roof areas exhibit different conditions, it should be brought to our attention for remedial work. This uplift test is not a roof top inspection. A final roof inspection must be conducted by the building official for approval. The test results presented reflect the condition of the roof system at the time of the test. These results are time and sample dependent since roof conditions are continuously changing due to exposure to the elements. Federal Engineering & Testing, Inc. is an independent third party providing un -biased testing information and results and is not affiliated with our client nor do we have any financial interest in the project or determination of the test results. As mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of clients, and authorization for publication of statements, conclusions or extracts from or regarding our reports is reserved pending our written approval. We aosreciate^the. dp►iortunity to be of service to you at this phase of your project. If you have any questions or coml3W4,..pleasg6194:11.5 a call. It has been a pleasure working with you and look forward to doing so again in the n°eerffutt?re. .S:ic§r:ly, rsI w :': Y t •% i 'lire j �� ��� -�Ir" .� Keith LeBlanc, P:E. 7. !'-Zy_1� .� r • Federal E,ngcneering &Jesting, Inc. Florid:E2dg. No. 59394 t‘` �~ Certificateoi 7;uthdrizatioh # 5471 Miami -Dade County Certification # 16-0203.07 Construction Material Engineering Council American Concrete Institute MIAMFDADE COUNTY Miami Dade Florida Department County of Transportation 1 L Elta4mi f - k- , at* —.4 -f a= 0.1(w)= 0.1( 40 ') = 4.0 ' a= 0.4 (h)= 0.4( 15 ') = 6.0' Perimeter Dimensions : 4.0 ' Figure R301.2(7) Componet & Cladding Pressure Zones Corner Area: N/A S.F. = N/A tests Perimeter Area: 32 S.F. = 1 tests Field Area: 68 S.F. = 1 tests Ridge Caps: 2 = 1 tests Total Tests Performed: = 3 *All dimensions are approximate* Test Location Sketch ENGINEERING Q N Federal Engineering & Testing Inc. 250 SW 13th AVE Pompano Beach, FL 33069 (954) 784-2941 Client: Paul Bange Roofing Test: TAS -106 Tile Uplift Test (Test location sketch is not to scale) Project: Proposed Roof: Bach Residence Project Address: 9304 NE 5th Avenue Miami Shores, FL 33138 J