RF-17-1322 (2)ENGINEERING 4225 SW 71 Ave Miami. FI 33155 Tel: 786-398-9179 Fax: 786-800-2627 al roofinspection@gmail.com LAB CERTIFICATION #16-0510.15 SITE SPECIFIC INFORMATION UPLIFT TEST — TAS #106 12/06/2017 Roofing Contractor ACEBO ROOFING Job Address 10634 NE 10 CT Owner's Name ART SALOW Type of Tile BEL AIR ARROWHEAD GRAY Approximate Roof Height 12' feet Approximate Square Footage of Roof 22 Date Tested 12/06/2017 Contact Name MADELINE Roof Pitch 3/12 ft2 Number of Tests 63 Permit # RF -5-17-1322 Date Installed Type of Access to Roof LADDER Required Testing Force 35 Lbs Testing Equipment F.G.E.100 Phone # 786-402-9762 LOCATION # OF TEST PASS # OF TEST FAIL Corner 10 Tests 10 Pass Test Fail Perimeter 16 Tests 16 Pass Test Fail Field 22 Tests 22 Pass Test Fail Ridge 15 Tests 15 Pass Test Fail TOTAL 63 Tests 63 Pass o Test 0 Fail IN ACCORDANCE WITH THE CRITERIA OF PROTOCOL PA 106, THIS ROOF ASSEMBLY HAS PASSED THE STATIC UPLIFT QUALITY CONTROL TEST. THIS TAS 106 TEST HAS BEEN PERFORMED IN FULL ACCORDANCE TO THE REQUIREMENTS OF DADE COUNTRY, WITH NO DEVIATIONS. THIS REPORT IS NOT GUARANTEED IN CASE OF CASE OF NATURAL DISASTERS. THIS REPORT IT 15 NOT VALID FOR INSURANCE CLAIMS. YENAN T. LEYVA PE67416 .1